درایو 15 کیلووات، سه فاز سری ATV212
×
درایو 15 کیلووات، سه فاز سری ATV212

ATV212HD15N4

درایو 15 کیلووات، سه فاز سری ATV212

variable speed drive ATV212 - 15kW - 20hp - 480V - 3ph - EMC - IP21

مشخصات کامل
device short name
ATV212
device short name
product destination
Asynchronous motors
product destination
network number of phases
3 phases
network number of phases
motor power kW
15 kW
motor power kW
motor power hp
20 hp
motor power hp
supply voltage limits
323…528 V
supply voltage limits
supply frequency
50...60 Hz - 5...5 %
supply frequency
line current
22.8 A at 480 V 28.5 A at 380 V
line current
سری
Altivar 212
range of product
product or component type
Variable speed drive
product or component type
product specific application
Pumps and fans in HVAC
product specific application
communication port protocol
BACnet Modbus METASYS N2 APOGEE FLN LonWorks
communication port protocol
[Us] rated supply voltage
380...480 V - 15...10 %
[Us] rated supply voltage
EMC filter
Class C2 integrated
EMC filter
IP degree of protection
IP21
IP degree of protection
apparent power
23.2 kVA at 380 V
apparent power
continuous output current
30.5 A at 380 V 30.5 A at 460 V
continuous output current
maximum transient current
33.6 A for 60 s
maximum transient current
speed drive output frequency
0.5…200 Hz
speed drive output frequency
speed range
1…10
speed range
speed accuracy
+/- 10 % of nominal slip 0.2 Tn to Tn
speed accuracy
local signalling
1 LED (red) for DC bus energized
local signalling
output voltage
<= power supply voltage
output voltage
isolation
Electrical between power and control
isolation
type of cable
Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
type of cable
electrical connection
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14 L1/R, L2/S, L3/T: terminal 25 mm² / AWG 3
electrical connection
tightening torque
0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) 4.5 N.m, 40 lb.in (L1/R, L2/S, L3/T)
tightening torque
supply
Internal for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection Internal : 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection
supply
sampling duration
2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog
sampling duration
response time
FM 2 ms, tolerance +/- 0.5 ms for analog output(s) FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s) RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
response time
accuracy
+/- 0.6 % (VIA) for a temperature variation 60 °C +/- 0.6 % (VIB) for a temperature variation 60 °C +/- 1 % (FM) for a temperature variation 60 °C
accuracy
linearity error
VIA: +/- 0.15 % of maximum value for input VIB: +/- 0.15 % of maximum value for input FM: +/- 0.2 % for output
linearity error
analogue output type
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
analogue output type
discrete output type
Configurable relay logic: (FLA, FLC) NO - 100000 cycles Configurable relay logic: (FLB, FLC) NC - 100000 cycles Configurable relay logic: (RY, RC) NO - 100000 cycles
discrete output type
minimum switching current
3 mA at 24 V DC for configurable relay logic
minimum switching current
maximum switching current
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R) 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
maximum switching current
discrete input type
F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
discrete input type
discrete input logic
Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1) Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
discrete input logic
dielectric strength
3535 V DC between earth and power terminals 5092 V DC between control and power terminals
dielectric strength
insulation resistance
>= 1 mOhm 500 V DC for 1 minute
insulation resistance
frequency resolution
Display unit: 0.1 Hz Analog input: 0.024/50 Hz
frequency resolution
communication service
Time out setting from 0.1 to 100 s Read device identification (43) Monitoring inhibitable Write single register (06) Write multiple registers (16) 2 words maximum Read holding registers (03) 2 words maximum
communication service
option card
Communication card for LonWorks
option card
power dissipation in W
625 W
power dissipation in W
air flow
206 m3/h
air flow
functionality
Mid
functionality
specific application
HVAC
specific application
Variable speed drive application selection
Compressor for scroll Building - HVAC Fan Building - HVAC Pump Building - HVAC
Variable speed drive application selection
Motor power range AC-3
15…25 kW at 380…440 V 3 phases 15…25 kW at 480…500 V 3 phases
Motor power range AC-3
motor starter type
Variable speed drive
motor starter type
discrete output number
2
discrete output number
analogue input number
2
analogue input number
analogue input type
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
analogue input type
analogue output number
1
analogue output number
physical interface
2-wire RS 485
physical interface
connector type
1 open style 1 RJ45
connector type
transmission rate
9600 bps or 19200 bps
transmission rate
transmission frame
RTU
transmission frame
number of addresses
1…247
number of addresses
data format
8 bits, 1 stop, odd even or no configurable parity
data format
type of polarization
No impedance
type of polarization
asynchronous motor control profile
Flux vector control without sensor, standard Voltage/frequency ratio, 2 points Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 5 points
asynchronous motor control profile
torque accuracy
+/- 15 %
torque accuracy
transient overtorque
120 % of nominal motor torque +/- 10 % for 60 s
transient overtorque
acceleration and deceleration ramps
Linear adjustable separately from 0.01 to 3200 s Automatic based on the load
acceleration and deceleration ramps
motor slip compensation
Automatic whatever the load Not available in voltage/frequency ratio motor control Adjustable
motor slip compensation
switching frequency
6...16 kHz adjustable 12...16 kHz with derating factor
switching frequency
nominal switching frequency
12 kHz
nominal switching frequency
braking to standstill
By DC injection
braking to standstill
network frequency
47.5...63 Hz
network frequency
prospective line Isc
22 kA
prospective line Isc
protection type
Overheating protection: drive Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor
protection type
width
245 mm
width
height
330 mm
height
depth
190 mm
depth
net weight
11.65 kg
net weight
pollution degree
2 conforming to IEC 61800-5-1
pollution degree
IP degree of protection
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529 IP21 conforming to EN/IEC 61800-5-1 IP21 conforming to EN/IEC 60529 IP41 on upper part conforming to EN/IEC 61800-5-1 IP41 on upper part conforming to EN/IEC 60529
IP degree of protection
vibration resistance
1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8
vibration resistance
shock resistance
15 gn for 11 ms conforming to IEC 60068-2-27
shock resistance
environmental characteristic
Classes 3C1 conforming to IEC 60721-3-3 Classes 3S2 conforming to IEC 60721-3-3
environmental characteristic
noise level
54 dB conforming to 86/188/EEC
noise level
operating altitude
1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 1000 m without derating
operating altitude
relative humidity
5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3
relative humidity
ambient air temperature for operation
-10…40 °C (without derating) 40…50 °C (with derating factor)
ambient air temperature for operation
operating position
Vertical +/- 10 degree
operating position
product certifications
CSA UL C-Tick NOM 117
product certifications
marking
CE
marking
standards
IEC 61800-3 category C2 EN 61800-3 category C3 IEC 61800-3 category C3 IEC 61800-5-1 EN 61800-3 environments 2 category C1 EN 55011 class A group 1 IEC 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C2 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 EN 61800-5-1 UL Type 1 IEC 61800-3 environments 2 category C3 EN 61800-3 category C2 EN 61800-3 environments 1 category C3 IEC 61800-3 EN 61800-3 environments 1 category C2 EN 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C1 EN 61800-3 IEC 61800-3 environments 2 category C1 EN 61800-3 environments 1 category C1
standards
assembly style
With heat sink
assembly style
electromagnetic compatibility
Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
electromagnetic compatibility
regulation loop
Adjustable PI regulator
regulation loop
ambient air temperature for storage
-25…70 °C
ambient air temperature for storage
Unit Type of Package 1
PCE
Unit Type of Package 1
Number of Units in Package 1
1
Number of Units in Package 1
Package 1 Weight
11.646 kg
Package 1 Weight
Package 1 Height
27.5 cm
Package 1 Height
Package 1 width
39.5 cm
Package 1 width
Package 1 Length
30 cm
Package 1 Length
Unit Type of Package 2
P06
Unit Type of Package 2
Number of Units in Package 2
4
Number of Units in Package 2
Package 2 Weight
59.584 kg
Package 2 Weight
Package 2 Height
73.5 cm
Package 2 Height
Package 2 width
80 cm
Package 2 width
Package 2 Length
60 cm
Package 2 Length
Warranty
18 months
Warranty