LV429844
کلید قابل تنظیم 3 پل 40 آمپر با قدرت قطع 50 کیلوآمپر
circuit breaker ComPact NSX100N, 50 kA at 415 VAC, TMD trip unit 40 A, 3 poles 3d
مشخصات کامل
گروه
ComPact
range
نام محصول
ComPact NSX
product name
سری
ComPact NSX100...250
range of product
device short name
NSX100N
device short name
product or component type
Circuit breaker
product or component type
device application
Distribution
device application
Number of poles
3P
Number of poles
protected poles description
3t
protected poles description
[In] rated current
40 A at 40 °C
[In] rated current
[Ue] rated operational voltage
690 V AC 50/60 Hz
[Ue] rated operational voltage
network type
AC
network type
network frequency
50/60 Hz
network frequency
suitability for isolation
Yes conforming to EN/IEC 60947-2
suitability for isolation
utilisation category
Category A
utilisation category
[Icu] rated ultimate short-circuit breaking capacity
85 kA at 240 V AC 50/60 Hz conforming to UL 508
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
50 kA at 480 V AC 50/60 Hz conforming to UL 508
36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Icu] rated ultimate short-circuit breaking capacity
Performance level
N 50 kA 415 V AC
Performance level
trip unit name
TM-D
trip unit name
trip unit technology
Thermal-magnetic
trip unit technology
trip unit protection functions
LI
trip unit protection functions
control type
Toggle
control type
Circuit breaker mounting mode
Fixed
Circuit breaker mounting mode
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Ui] rated insulation voltage
[Uimp] rated impulse withstand voltage
8 kV
[Uimp] rated impulse withstand voltage
[Ics] rated service short-circuit breaking capacity
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
mechanical durability
50000 cycles
mechanical durability
electrical durability
10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2
electrical durability
mounting support
Backplate
mounting support
upside connection
Front
upside connection
downside connection
Front
downside connection
connection pitch
35 mm
connection pitch
protection type
L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
protection type
trip unit rating
40 A at 40 °C
trip unit rating
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable
Long-time pick-up adjustment type Ir (thermal protection)
[Ir] long-time protection pick-up adjustment range
0.7...1 x In
[Ir] long-time protection pick-up adjustment range
Long-time protection delay adjustment type tr
Fixed
Long-time protection delay adjustment type tr
[tr] long-time protection delay adjustment range
120…400 s at 1.5 x In
15 s at 6 x Ir
[tr] long-time protection delay adjustment range
Short-time protection pick-up adjustment type Isd
Fixed
Short-time protection pick-up adjustment type Isd
[Isd] Short-time protection pick-up adjustment range
500 A
[Isd] Short-time protection pick-up adjustment range
Short-time protection delay adjustment type tsd
Fixed
Short-time protection delay adjustment type tsd
earth-leakage protection
Without
earth-leakage protection
Number of slots for electrical auxiliaries
5 slot(s)
Number of slots for electrical auxiliaries
Width (W)
105 mm
Width (W)
Height (H)
161 mm
Height (H)
Depth (D)
86 mm
Depth (D)
net weight
2.05 kg
net weight
standards
EN/IEC 60947
standards
product certifications
CCC
EAC
Marine
product certifications
overvoltage category
Class II
overvoltage category
electrical shock protection class
Class II
electrical shock protection class
pollution degree
3 conforming to IEC 60664-1
pollution degree
IP degree of protection
IP40 conforming to IEC 60529
IP degree of protection
IK degree of protection
IK07 conforming to IEC 62262
IK degree of protection
ambient air temperature for operation
-25…70 °C
ambient air temperature for operation
ambient air temperature for storage
-50…85 °C
ambient air temperature for storage
relative humidity
0…95 %
relative humidity
operating altitude
0...2000 m without derating
2000 m...5000 m with derating
operating altitude
Unit Type of Package 1
PCE
Unit Type of Package 1
Number of Units in Package 1
1
Number of Units in Package 1
Package 1 Weight
1.808 kg
Package 1 Weight
Package 1 Height
11.5 cm
Package 1 Height
Package 1 width
14 cm
Package 1 width
Package 1 Length
19 cm
Package 1 Length
Unit Type of Package 2
S03
Unit Type of Package 2
Number of Units in Package 2
4
Number of Units in Package 2
Package 2 Weight
7.653 kg
Package 2 Weight
Package 2 Height
30 cm
Package 2 Height
Package 2 width
30 cm
Package 2 width
Package 2 Length
40 cm
Package 2 Length
Warranty
18 months
Warranty