VPL12N
رگولاتور خازنی 12 پله
Power Factor controller, PowerLogic PFC Controller, VPL 12
مشخصات کامل
گروه
PowerLogic
range
نام محصول
PowerLogic PFC Controller
product name
device short name
VPL12
device short name
product or component type
Power factor controller
product or component type
number of step output contacts
12
number of step output contacts
[Us] rated supply voltage
90...550 V AC
<= 999 kV AC with external VT
[Us] rated supply voltage
measurement current
0…5 A
measurement current
measurement voltage
90…550 V AC 50/60 Hz
measurement voltage
operating mode
Manual or automatic
operating mode
number of quadrant operation for generator application
4
number of quadrant operation for generator application
device connection
Communication protocol: Modbus interface: RS485
device connection
input function
Switch: 1 x dry contact
input function
colour code
Front: dark grey RAL 7016
colour code
display type
Backlit LCD
display type
display size
56 x 25 mm
display size
function available
Manual programming
Automatic initialisation
Automatic detection
Advanced programming (expert)
Any step sequence
function available
metering type
Power factor and displacement PF (signed, four quadrant)
Total current harmonic distortion THD (I)
Power factor average over lifetime
Temperature maximum
Phase current I1, I2, I3 RMS on load
Active power P, P1, P2, P3 on load
Reactive power Q, Q1, Q2, Q3 on load
Apparent power S, S1, S2, S3 on load
Voltage U21, U32, U13, V1, V2, V3 on load
metering type
type of measurement
Capacitor current overload Irms/I1
Individual voltage harmonic
Power factor
Operating time
Cos ?
Ambient temperature inside the cubicle
Tan ?
type of measurement
information displayed
Number of switching cycles per step
Individual step size in kVAr
Remaining step capacity in %
information displayed
type of alarms
Step power loss (< 75 %) / Action: message and alarm contact + step blocked
Step faulty / Action: message and alarm contact + step blocked
High current (> 6 A CT) / Action: message and alarm contact
Hunting (unstable regulation) / Action: message and alarm contact + step blocked
Low current (< 15 mA CT) / Action: message and alarm contact
Overcompensation / Action: message and alarm contact
Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off
Overtemperature (50 °C) / Action: message and alarm contact + step switched off
Overtemperature (30 °C) / Action: fan switch
Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped
Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched off
type of alarms
data recording
5 alarms
data recording
Operational Hours alarm
100000 h without maintenance
Operational Hours alarm
Operational counter alarm
65000 cycles without maintenance
Operational counter alarm
input type
Phase to phase
Phase to neutral
Insensitive to CT polarity
Insensitive to phase rotation polarity
Current input CT...X/5 A and X/1 A
input type
output type
Control relay: 0.2 A 110 V DC
Control relay: 1 A 48 V DC
Control relay: 2 A 400 V AC 50/60 Hz
Control relay: 1 A 24 V DC
Control relay: 5 A 250 V AC 50/60 Hz
Control relay: 5 A 120 V AC 50/60 Hz
Fan: 5 A 250 V AC 50/60 Hz
Fan: 1 A 48 V DC
Alarm relay: 5 A 250 V AC 50/60 Hz
Alarm relay: 1 A 48 V DC
output type
Maximum at the common terminal
10 A
Maximum at the common terminal
settings operating mode
Automatic
Manual
settings operating mode
type of setting
Choice of stepping programs: auto
Choice of stepping programs: LIFO
Choice of stepping programs: linear
Delay between 2 successive switch on the same step: 5...1200 s
Step configuration programming: auto
Step configuration programming: off
Step configuration programming: fixed
Target cos phi: 0.7 inductive...0.7 capacitive
Target cos phi: dual cos ?
type of setting
measurement accuracy
Voltage +/- 1 %
Current +/- 1 %
Frequency +/- 1 %
Energy (P,Q,S) +/- 2 %
Cos ? +/- 2 %
Total voltage harmonic distortion THD (U) +/- 2 %
Individual voltage harmonic +/- 3 %
Temperature +/- 3 °C
measurement accuracy
time delay range
1...6500 s (on reconnection)
1...6500 s (on response)
time delay range
provided equipment
User manual
provided equipment
mounting mode
Flush-mounted
mounting mode
mounting support
Panel - thickness: 1…3 mm
mounting support
mounting location
In cabinet
mounting location
cut-out dimensions
138 x 138 mm
cut-out dimensions
height
144 mm
height
width
144 mm
width
depth
58 mm
depth
net weight
0.6 kg
net weight
standards
IEC 61000-6-4
UL 61010-1
EN 61010-1
IEC 61000-6-2
IEC 61326-1
standards
product certifications
EAC
NRTL
cNRTL
CE
product certifications
IP degree of protection
Front face: IP41
Rear face: IP20
IP degree of protection
operating altitude
<= 2000 m
operating altitude
ambient air temperature for operation
-20…60 °C
ambient air temperature for operation
ambient air temperature for storage
-40…85 °C
ambient air temperature for storage
Unit Type of Package 1
PCE
Unit Type of Package 1
Number of Units in Package 1
1
Number of Units in Package 1
Package 1 Weight
724.0 g
Package 1 Weight
Package 1 Height
9.2 cm
Package 1 Height
Package 1 width
17.7 cm
Package 1 width
Package 1 Length
18.4 cm
Package 1 Length
Unit Type of Package 2
P06
Unit Type of Package 2
Number of Units in Package 2
64
Number of Units in Package 2
Package 2 Weight
58.408 kg
Package 2 Weight
Package 2 Height
75 cm
Package 2 Height
Package 2 width
60 cm
Package 2 width
Package 2 Length
80 cm
Package 2 Length
Unit Type of Package 3
S03
Unit Type of Package 3
Number of Units in Package 3
8
Number of Units in Package 3
Package 3 Weight
6.301 kg
Package 3 Weight
Package 3 Height
30 cm
Package 3 Height
Package 3 width
30 cm
Package 3 width
Package 3 Length
40 cm
Package 3 Length